Description
Massive 45kVA Three-Phase Power Plant
The Energydock Large 3Ø Energy Pod (45kVA/49.2kWh) is engineered for high-demand environments where balanced, heavy-duty power is essential. Utilizing three Victron Quattro 48/15000 units, the system delivers a continuous output of 45,000 VA (36,000 W) across three phases. With a staggering 25,000W peak power capacity per phase (75,000W total), it effortlessly handles the most intensive startup surges from industrial motors, large-scale HVAC systems, and production machinery.
Advanced Dual AC Input & Generator Control
Built on the flagship Quattro architecture, this system includes two independent AC inputs per phase. This allows for the simultaneous connection of the utility grid and a backup generator. The Pod intelligently monitors both sources and can automatically transition between them, ensuring total operational continuity. The integrated PowerAssist technology can also supplement a limited grid or generator supply with battery power during peak demand periods.
Industrial Storage & Utility-Grade Safety
Equipped with a 49.2kWh Storagedock LiFePO4 battery bank (960 Ah), this system provides 39.3kWh of usable energy at 80% Depth of Discharge. Safety is managed at an industrial scale via a 1000A motorized and programmed circuit breaker and internal 300A module fuses, protecting the high-capacity Grade A Prismatic cells from any electrical fault.
Precision Climate & Management Suite
- Active Temperature Management: An integrated SDC 115-1 climate control unit (1500W cooling / 500W heating) maintains an optimal internal environment. This ensures reliable operation in temperatures from -40°C to 50°C, significantly extending the lifespan of the lithium cells and electronics.
- Premium Oversight: Includes the Victron Cerbo GX ensemble and GX Touch 70 display for professional on-site control and 24/7 remote monitoring via the Victron Remote Management (VRM) portal.
- Flagship 2.5m Enclosure: The ground-mountable metal enclosure (IP55) provides the necessary thermal mass and space for this high-output configuration while offering maximum protection against the elements.
Key Product Specifications
- Inverters: 3 x Victron Quattro 48/15000/200-100 (Three-Phase Configuration)
- Battery Capacity: 49.2kWh (960 Ah) Total Energy
- Usable Energy: 39.3kWh (@ 80% DoD)
- Continuous Power: 45,000 VA / 36,000 W (15,000 VA per phase @ 25°C)
- Peak Power: 25,000 W per phase (75,000 W Total)
- AC Inputs: Dual AC Inputs (Grid + Generator) per phase
- Dimensions: 2524mm (L) x 960mm (W) x 1621mm (H)
- Warranty: 10-year warranty on Victron inverters and Storagedock battery
Focus Keyphrase: 45kVA 49.2kWh Three Phase Large Energy Pod
Meta Description: Deploy industrial-scale power with the 45kVA / 49.2kWh Large Three Phase Energy Pod. Dual AC inputs, 75kW peak power, and active climate control. 10-year warranty included.
| LARGE (4 BATTERY) 3Ø ENERGY POD GENERAL SPECIFICATIONS | |
|---|---|
| Product code | EPL3-45/49/Q |
| Dimensions | 2524mm (length) x 960mm (width) x 1621mm (height) |
| Enclosure | Ground mountable metal enclosure |
| Installation | Indoor or outdoor |
| VICTRON QUATTRO 48/15000/200-100 INVERTER/CHARGER (x3) | |
| PowerControl / PowerAssist | Yes |
| Integrated Transfer switch | Yes |
| AC Inputs (x2) | Input Voltage: 187 – 250 VAC / Frequency 50 – 60 Hz |
| Maximum Feed through current (per phase) | 2 x 100A |
| INVERTER | |
| DC input voltage range | 38 V – 66 V |
| Output | 230 VAC ± 2% / Frequency: 50 Hz ± 0.1% |
| Continuous output power at 25˚C | 15 000 VA / 12 000 W per phase |
| Continuous output power at 40˚/65˚C | 10 000 W / 7 000 W per phase |
| Max apparent feed-in power | 15 000 VA per phase |
| Peak power | 25 000 W per phase |
| Maximum efficiency | 96% |
| Zero load power | 330 W |
| Zero load power in AES mode | 225 W |
| Zero load power in search mode | 60 W |
| CHARGER | |
| AC input | Input voltage range: 187 – 256 VAC / Input frequency: 45–65 Hz |
| Charge voltage absorption | 56.2 VDC |
| Charge voltage float | 56.0 VDC |
| Storage mode | 52.8 VDC |
| Max battery charge current | 200 A per phase |
| Battery temperature sensor | Yes |
| GENERAL | |
| Auxillary output | 50 A per phase |
| Programmable relay | Yes |
| Protection | a) output short circuit b) overload c) battery voltage too high d) battery voltage too low e) temperature too high f) 230 VAC on inverter output g) input voltage ripple too high |
| VE.Bus communication Port | For parallel & 3 phase operation, remote monitoring, system integration |
| General purpose com. Port | 2 x |
| Remote on-off | Yes |
| Operating temperature | -40 to +65°C fan assisted cooling / Humidity max 95% |
| STANDARDS | |
| Safety | EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1 |
| Emission, Immunity | EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3, EN-IEC61000-3-3 |
| VICTRON CERBO GX DEVICE – REMOTE MANAGEMENT & PROGRAMMING | |
| Supply voltage | 8 – 70 VDC |
| VE.Direct ports (always isolated) | 3 |
| VE.Bus (always isolated) | 2 paralleled RJ45 sockets |
| VE.Can | Yes – non isolated |
| Operating temperature range | -20 to +50°C |
| Cable length | 2 m |
| GX TOUCH 50 / GX TOUCH 70 | |
| Display Resolution | GX Touch 50: 800 x 480, GX Touch 70: 1024 x 600 |
| CLIMATE CONTROL UNIT | |
| Model | SDC 115 – 1 |
| Cooling Capacity | 1500 W |
| Voltage | DC 48V |
| Rated Power | 360 W |
| Refrigerant | R134a |
| Heating Capacity | 500 W |
| Working Temperature | -40 – 50°C |
| Noise | 62 dB |
| Weight | 26 kg |
| IP Rating | IP55 |
| STORAGEDOCK LV-COM 49.2/900 LiFePO₄ BATTERY | |
| Battery type | Grade A LiFePO₄ Prismatic cells |
| Nominal voltage | 51.2 VDC |
| Nominal capacity | 960 Ah |
| Total energy capacity | 49.2 kWh |
| Energy capacity at 80% DoD | 39.3 kWh |
| Maximum & constant current | 900 A |
| Maximum charge current | 915 A for 5 seconds |
| Maximum discharge current | 1065 A for 5 seconds / 915 A for 30 seconds |
| Protection | 1000 A motorized and programmed circuit breaker |
| Internal module fuse | 300 A (ANL) |
| Warranty cycle life | 6000 cycles @0.5C 80% depth of discharge |
| WARRANTIES | |
| Victron inverters | 10 year warranty |
| Victron Cerbo GX device | 10 year warranty |
| Storagedock battery | 10 years / 6000 cycles @ 80% DoD, whichever occurs first |