Description
Unmatched Three-Phase Endurance
The Energydock Large 3Ø Energy Pod (15kVA/65.6kWh) is engineered for users who require significant energy reserves without compromising on phase stability. Utilizing three Victron Multiplus II 48/5000 inverter/chargers, the system delivers a continuous output of 15,000 VA (12,000 W) balanced across three phases. With a 9,000W peak power capacity per phase, it easily manages heavy startup loads such as industrial pumps, large-scale climate control systems, and commercial machinery.
Massive Energy Reserves & Utility-Grade Safety
Equipped with an expansive 65.6kWh Storagedock LiFePO4 battery bank (1280 Ah), this Pod provides a substantial 52.5kWh of usable energy at 80% Depth of Discharge. Safety is paramount at this scale; the system includes a 1000A motorized and programmed circuit breaker and internal 300A module fuses to protect the high-capacity Grade A Prismatic cells, ensuring long-term reliability and peace of mind.
Advanced Climate & Monitoring Suite
- Active Temperature Management: An integrated SDC 115-1 climate control unit (1500W cooling / 500W heating) maintains a stable internal environment between -40°C and 50°C, protecting sensitive electronics and maximizing the 6000-cycle battery life.
- Professional Management: Includes the Victron Cerbo GX ensemble and GX Touch 70 display for advanced on-site control and 24/7 remote monitoring via the Victron Remote Management (VRM) portal.
- Extended Enclosure: The 2.5-meter ground-mountable metal enclosure (IP55) provides superior thermal mass and airflow, specifically designed to house the maximum-capacity battery configuration.
Key Product Specifications
- Inverters: 3 x Victron Multiplus II 48/5000/70-50
- Battery Capacity: 65.6kWh (1280 Ah) Total Energy
- Usable Energy: 52.5kWh (@ 80% DoD)
- Continuous Power: 15,000 VA / 12,000 W (5,000 VA per phase @ 25°C)
- Peak Power: 9,000 W per phase
- Climate Control: SDC 115-1 Unit (1500W Cooling / 500W Heating)
- Dimensions: 2524mm (L) x 960mm (W) x 1621mm (H)
- Warranty: 10-year warranty on Victron inverters, Cerbo GX, and Storagedock battery
| LARGE (4 BATTERY) 3Ø ENERGY POD GENERAL SPECIFICATIONS | |
|---|---|
| Product code | EPL3-15/65/M |
| Dimensions | 2524mm (length) x 960mm (width) x 1621mm (height) |
| Enclosure | Ground mountable metal enclosure |
| Installation | Indoor or outdoor |
| VICTRON MULTIPLUS II 48/5000/70-50 INVERTER/CHARGER (x3) | |
| PowerControl / PowerAssist | Yes |
| Transfer switch | 50 A per phase |
| Maximum AC input current | 50 A per phase |
| INVERTER | |
| DC input voltage range | 48 V – 38 – 66 V |
| Output | 230 VAC ± 2% / Frequency: 50 Hz ± 0.1% |
| Continuous output power at 25˚C | 5 000 VA / 4 000 W per phase |
| Continuous output power at 40˚/60˚C | 3 700 W / 3 000 W per phase |
| Max apparent feed-in power | 5000 VA per phase |
| Peak power | 9 000 W per phase |
| Maximum efficiency | 96% |
| Zero load power | 54 W |
| Zero load power in AES mode | 36 W |
| Zero load power in search mode | 6 W |
| CHARGER | |
| AC input | Input voltage range: 187 – 256 VAC / Input frequency: 45–65 Hz |
| Charge voltage absorption | 56.2 VDC |
| Charge voltage float | 56.2 VDC |
| Storage mode | 52.8 VDC |
| Max battery charge current | 70 A per phase DC |
| Battery temperature sensor | Yes |
| GENERAL | |
| Auxillary output | 32 A |
| Programmable relay | Yes |
| Protection | a) output short circuit b) overload c) battery voltage too high d) battery voltage too low e) temperature too high f) 230 VAC on inverter output g) input voltage ripple too high |
| VE.Bus communication Port | For parallel & 3 phase operation, remote monitoring, system integration |
| General purpose com. Port | 2 x |
| Remote on-off | Yes |
| Operating temperature | -40 to +65°C fan assisted cooling / Humidity max 95% |
| STANDARDS | |
| Safety | EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1 |
| Emission, Immunity | EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3, EN-IEC61000-3-3 |
| VICTRON CERBO GX DEVICE – REMOTE MANAGEMENT & PROGRAMMING | |
| Supply voltage | 8 – 70 VDC |
| VE.Direct ports (always isolated) | 3 |
| VE.Bus (always isolated) | 2 paralleled RJ45 sockets |
| VE.Can | Yes – non isolated |
| Operating temperature range | -20 to +50°C |
| Cable length | 2 m |
| GX TOUCH 50 / GX TOUCH 70 | |
| Display Resolution | GX Touch 50: 800 x 480, GX Touch 70: 1024 x 600 |
| CLIMATE CONTROL UNIT | |
| Model | SDC 115 – 1 |
| Cooling Capacity | 1500 W |
| Voltage | DC 48V |
| Rated Power | 360 W |
| Refrigerant | R134a |
| Heating Capacity | 500 W |
| Working Temperature | -40 – 50°C |
| Noise | 62 dB |
| Weight | 26 kg |
| IP Rating | IP55 |
| STORAGEDOCK LV-COM 65.6/1000 LiFePO₄ BATTERY | |
| Battery type | Grade A LiFePO₄ Prismatic cells |
| Nominal voltage | 51.2 VDC |
| Nominal capacity | 1280 Ah |
| Total energy capacity | 65.6 kWh |
| Energy capacity at 80% DoD | 52.5 kWh |
| Maximum & constant current | 1060 A |
| Maximum charge current | 1100 A for 5 seconds |
| Maximum discharge current | 1300 A for 5 seconds / 1100 A for 30 seconds |
| Protection | 1000 A motorized and programmed circuit breaker |
| Internal module fuse | 300 A (ANL) |
| Warranty cycle life | 6000 cycles @0.5C 80% depth of discharge |
| WARRANTIES | |
| Victron inverters | 10 year warranty |
| Victron Cerbo GX device | 10 year warranty |
| Storagedock battery | 10 years / 6000 cycles @ 80% DoD, whichever occurs first |
| Climate Control unit | 3 year warranty |