Description
Redundant Three-Phase Power Management
The Energydock Medium 3Ø Energy Pod (24kVA) is designed for sites where power stability and redundancy are paramount. Utilizing three Victron Quattro 48/8000 inverter/chargers, the system delivers a continuous output of 24,000 VA (19,200 W) balanced across three phases. Its massive 48,000W total peak power (16,000W per phase) ensures that even the most demanding three-phase motor loads start without a hitch.
Dual-Input Generator & Grid Integration
Unique to the Quattro series, each phase features dual AC inputs. This allows the system to remain connected to the utility grid and a backup generator simultaneously. The Pod intelligently switches to the active power source, ensuring uninterrupted operation for sensitive commercial equipment or large-scale residential HVAC systems.
Massive Storage & Industrial Safety
Equipped with a 32.8kWh Storagedock LiFePO4 battery bank (640 Ah), this pod provides 26.2kWh of usable energy at 80% Depth of Discharge. Safety is managed by a 1000A motorized and programmed circuit breaker, providing high-level protection for the high-capacity lithium cells.
Climate Controlled Reliability
- Active Climate Unit: An integrated SDC 115-1 climate control unit (1500W cooling) maintains the internal temperature between -40°C and 50°C, protecting your investment from the South African heat and ensuring battery longevity.
- Victron Cerbo GX & Touch 70: Includes the full GX ensemble for professional on-site control and 24/7 remote monitoring via the VRM portal.
Key Product Specifications
- Inverters: 3 x Victron Quattro 48/8000/110-100 (Three-Phase Configuration).
- Battery Capacity: 32.8kWh (640 Ah) Total Energy.
- Usable Energy: 26.2kWh (@ 80% DoD).
- Continuous Power: 24,000 VA / 19,200 W (8,000 VA per phase @ 25°C).
- Peak Power: 16,000 W per phase (48,000 W Total).
- AC Inputs: Dual AC Inputs (Grid + Generator) per phase.
- Dimensions: 2075mm (L) x 960mm (W) x 1621mm (H).
- Warranty: 10-year warranty on Victron Inverters and Storagedock Battery.
| MEDIUM (3 BATTERY) 3Ø ENERGY POD GENERAL SPECIFICATIONS | |
|---|---|
| Product code | EPM3-24/32/Q |
| Dimensions | 2075mm (length) x 960mm (width) x 1621mm (height) |
| Enclosure | Ground mountable metal enclosure |
| Installation | Indoor or outdoor |
| VICTRON QUATTRO 48/8000/110-100 INVERTER/CHARGER (x3) | |
| PowerControl / PowerAssist | Yes |
| Integrated Transfer switch | Yes |
| AC Inputs (x2) | Input Voltage: 187 – 250 VAC |
| Maximum Feed through current (per phase) | 2 x 100 A |
| INVERTER | |
| DC input voltage range | 38 V – 66 V |
| Output | 230 VAC ± 2% / Frequency: 50 Hz ± 0.1% |
| Continuous output power at 25˚C | 8 000 VA / 6 400 W per phase |
| Continuous output power at 40˚/65˚C | 5 500 W / 3 600 W per phase |
| Max apparent feed-in power | 8 000 VA per phase |
| Peak power | 16 000 W per phase |
| Maximum efficiency | 96% |
| Zero load power | 180 W |
| Zero load power in AES mode | 120 W |
| Zero load power in search mode | 45 W |
| CHARGER | |
| AC input | 187 – 256 VAC / Frequency: 45–65 Hz |
| Charge voltage absorption | 56.2 VDC |
| Charge voltage float | 56.2 VDC |
| Storage mode | 52.8 VDC |
| Maximum battery charge current | 110 A per phase DC |
| Battery temperature sensor | Yes |
| GENERAL | |
| Auxillary output | 50 A |
| Programmable relay | Yes (x3) |
| Protection | a) output short circuit b) overload c) battery voltage too high d) battery voltage too low e) temperature too high f) 230 VAC on inverter output g) input voltage ripple too high |
| VE.Bus communication Port | For parallel & 3 phase operation, remote monitoring, system integration |
| General purpose com. Port | 2 x |
| Remote on-off | Yes |
| Operating temperature | -40 to +65°C fan assisted cooling / Humidity max 95% |
| STANDARDS | |
| Safety | EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1 |
| Emission, Immunity | EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3, EN-IEC 61000-3-3 |
| VICTRON CERBO GX DEVICE – REMOTE MANAGEMENT & PROGRAMMING | |
| Supply voltage | 8 – 70 VDC |
| VE.Direct ports (always isolated) | 3 |
| VE.Bus (always isolated) | 2 paralleled RJ45 sockets |
| VE.Can | Yes – non isolated |
| Operating temperature range | -20 to +50°C |
| Cable length | 2 m |
| GX TOUCH 50 / GX TOUCH 70 | |
| Display Resolution | GX Touch 50: 800 x 480, GX Touch 70: 1024 x 600 |
| CLIMATE CONTROL UNIT | |
| Model | SDC 115 – 1 |
| Cooling Capacity | 1500 W |
| Voltage | DC 48V |
| Rated Power | 360 W |
| Refrigerant | R134a |
| Heating Capacity | 500 W |
| Working Temperature | -40 – 50°C |
| Noise | 62 dB |
| Weight | 26 kg |
| IP Rating | IP55 |
| STORAGEDOCK LV-COM 32.8/600 LiFePO₄ BATTERY x3 | |
| Battery type | Grade A LiFePO₄ Prismatic cells |
| Nominal voltage | 51.2 VDC |
| Nominal capacity | 640 Ah x 3 = 1 920 Ah |
| Total energy capacity | 32.8 kWh x 3 = 98.4 kWh |
| Energy capacity at 80% DoD | 26.2 kWh x 3 = 78.6 kWh |
| Maximum & constant current | 600 A |
| Maximum charge current | 610 A for 5 seconds |
| Maximum discharge current | 710 A for 5 seconds / 610 A for 30 seconds |
| Protection | 1000 A motorized and programmed circuit breaker |
| Internal module fuse | 300 A (ANL) |
| Warranty cycle life | 6000 cycles @0.5C 80% depth of discharge |
| WARRANTIES | |
| Victron inverters | 10 year warranty |
| Victron Cerbo GX device | 10 year warranty |
| Storagedock battery | 10 years / 6000 cycles @ 80% DOD, whichever occurs first |
| Climate Control unit | 3 year warranty |