Description
Industrial-Grade Balanced Power
The Energydock Medium 3Ø Energy Pod is engineered for environments where three-phase stability and high energy reserves are non-negotiable. Utilizing three Victron Multiplus II 48/5000 inverter/chargers, the system delivers a continuous output of 15,000 VA (12,000 W) balanced across all three phases. With a 9,000W peak power capacity per phase, it effortlessly handles the high-startup currents of large-scale HVAC systems, industrial pumps, and commercial refrigeration.
Superior Energy Storage & Safety
This system features an expansive Storagedock 49.2kWh LiFePO4 battery bank (960 Ah), providing a substantial 39.3kWh of usable energy at 80% Depth of Discharge. To manage this massive power bank safely, the system is equipped with a 1000A motorized and programmed circuit breaker and internal 300A module fuses, offering protection levels far beyond standard residential setups.
Optimized for Harsh Environments
- Active Climate Management: The integrated SDC 115-1 climate control unit (1500W cooling / 500W heating) maintains the internal temperature between -40°C and 50°C, protecting your lithium cells and sensitive Victron electronics from environmental stress.
- Professional Remote Oversight: Features the Victron Cerbo GX ensemble and GX Touch 70 display for advanced on-site programming and comprehensive remote monitoring via the VRM portal.
- IP55 Rated Infrastructure: The 2-meter ground-mountable metal enclosure is designed for both indoor and outdoor installation, providing a secure, weather-proof home for your energy investment.
Key Product Specifications
- Inverters: 3 x Victron Multiplus II 48/5000/70-50.
- Battery Capacity: 49.2kWh (960 Ah) Total Energy.
- Usable Energy: 39.3kWh (@ 80% DoD).
- Continuous Power: 15,000 VA / 12,000 W (5,000 VA per phase @ 25°C.
- Peak Power: 9,000 W per phase.
- Protection: 1000A motorized & programmed circuit breaker.
- Dimensions: 2075mm (L) x 960mm (W) x 1621mm (H).
- Warranties: 10-year warranty on Victron inverters, Cerbo GX, and Storagedock battery.
| MEDIUM (3 BATTERY) 3Ø ENERGY POD GENERAL SPECIFICATIONS | |
|---|---|
| Product code | EPM3-15/49/M |
| Dimensions | 2075mm (length) x 960mm (width) x 1621mm (height) |
| Enclosure | Ground mountable metal enclosure |
| Installation | Indoor or outdoor |
| VICTRON MULTIPLUS II 48/5000/70-50 INVERTER/CHARGER (x3) | |
| PowerControl / PowerAssist | Yes |
| Transfer switch | 50 A per phase |
| Maximum AC input current | 50 A per phase |
| INVERTER | |
| DC input voltage range | 48 V – 38 – 66 V |
| Output | 230 VAC ± 2% / Frequency: 50 Hz ± 0.1% |
| Continuous output power at 25˚C | 5 000 VA / 4 000 W per phase |
| Continuous output power at 40˚/60˚C | 3 700 W / 3 000 W per phase |
| Maximum apparent feed-in power | 5 000 VA per phase |
| Peak power | 9 000 W per phase |
| Maximum efficiency | 96% |
| Zero load power | 54 W |
| Zero load power in AES mode | 36 W |
| Zero load power in search mode | 6 W |
| CHARGER | |
| AC input | Input voltage range: 187 – 256 VAC / Frequency: 45–65 Hz |
| Charge voltage absorption | 56.2 VDC |
| Charge voltage float | 56.2 VDC |
| Storage mode | 52.8 VDC |
| Maximum battery charge current | 70 A per phase DC |
| Battery temperature sensor | Yes |
| GENERAL | |
| Auxillary output | 32 A |
| Programmable relay | Yes |
| Protection | a) output short circuit b) overload c) battery voltage too high d) battery voltage too low e) temperature too high f) 230 VAC on inverter output g) input voltage ripple too high |
| VE.Bus communication Port | For parallel & 3 phase operation, remote monitoring, system integration |
| General purpose com. Port | 2 x |
| Remote on-off | Yes |
| Operating temperature | -40 to +65°C fan assisted cooling / Humidity max 95% |
| STANDARDS | |
| Safety | EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1 |
| Emission, Immunity | EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3, EN-IEC 61000-3-3 |
| VICTRON CERBO GX DEVICE – REMOTE MANAGEMENT & PROGRAMMING | |
| Supply voltage | 8 – 70 VDC |
| VE.Direct ports (always isolated) | 3 |
| VE.Bus (always isolated) | 2 paralleled RJ45 sockets |
| VE.Can | Yes – non isolated |
| Operating temperature range | -20 to +50°C |
| Cable length | 2 m |
| GX TOUCH 50 / GX TOUCH 70 | |
| Display Resolution | GX Touch 50: 800 x 480, GX Touch 70: 1024 x 600 |
| CLIMATE CONTROL UNIT | |
| Model | SDC 115 – 1 |
| Cooling Capacity | 1500 W |
| Voltage | DC 48V |
| Rated Power | 360 W |
| Refrigerant | R134a |
| Heating Capacity | 500 W |
| Working Temperature | -40 – 50°C |
| Noise | 62 dB |
| Weight | 26 kg |
| IP Rating | IP55 |
| STORAGEDOCK LV-COM 49.2/900 LiFePO₄ BATTERY x3 | |
| Battery type | Grade A LiFePO₄ Prismatic cells |
| Nominal voltage | 51.2 VDC |
| Nominal capacity | 960 Ah x 3 = 2 880 Ah |
| Total energy capacity | 49.2 kWh x 3 = 147.6 kWh |
| Energy capacity at 80% DoD | 39.3 kWh x 3 = 117.9 kWh |
| Maximum & constant current | 900 A |
| Maximum charge current | 915 A for 5 seconds |
| Maximum discharge current | 1 065 A for 5 seconds / 915 A for 30 seconds |
| Protection | 1000 A motorized and programmed circuit breaker |
| Internal module fuse | 300 A (ANL) |
| Warranty cycle life | 6000 cycles @0.5C 80% depth of discharge |
| WARRANTIES | |
| Victron inverters | 10 year warranty |
| Victron Cerbo GX device | 10 year warranty |
| Storagedock battery | 10 years / 6000 cycles @ 80% DOD, whichever occurs first |
| Climate Control unit | 3 year warranty |